0020140413_01 - 09/12 - Glow-wormINSTALLATIONi IMPORTANT: All the drawings dimensions are shown in mm.6 Appliance location6.1 Location6.1.1 Instru
0020140413_01 - 09/12 - Glow-worm7 Appliance installation 7.1 Scope of deliveryThe appliance is delivered in a single carton with a document pack an
0020140413_01 - 09/12 - Glow-wormGeneralThis boiler is designed for use as part of a sealed water central heating system with fully pumped circulation
0020140413_01 - 09/12 - Glow-worm7.4 Mounting • Make sure that the equipment used for implementing the installation is compatible with that of the a
0020140413_01 - 09/12 - Glow-worm7.4.2 Boiler hanginga DANGER: With regards to the Manual Handling Operations, 1992 Regulations, the following lift
0020140413_01 - 09/12 - Glow-worm8.2 Safety Discharge ValveBA321Key1 Discharge pipe 15mm o.d.2 Pressure relief valve PRV3 Draining outletA PRV ou
0020140413_01 - 09/12 - Glow-wormINCREASE PIPE SIZE 75 mm min.100 mm min.Washing machinetrap / waste442.5INSTALLATION- 14 -
0020140413_01 - 09/12 - Glow-worm9 Evacuation of combustion gas9.1 Regulationb ATTENTION: Only ue accessories supplied by Glow-worm must be used.D
0020140413_01 - 09/12 - Glow-worm9.2 Fluecongurationdescription9.2.1 HorizontalconcentricueØ60/100mm orØ80/125mm(C13typeinstallation
0020140413_01 - 09/12 - Glow-worm9.2.3 Multipleboilerchimneyue Ø60/100mm(C43typeinstallation)b ATTENTION:The ue connecting from the applia
0020140413_01 - 09/12 - Glow-worm10.2 Main board1 2 330mmmaxKey1 Connector2 Electricalwires3 Insulation• Keep a distance of a maximum of 30 mm b
0020140413_01 - 09/12 - Glow-worm10.3.2 230V permanent supply + 230V system controlsa DANGER: All cables connected to the appliance should be perman
0020140413_01 - 09/12 - Glow-worm10.6 Wiring diagram1102113124135146157168179181 23 410 9 8 7 6 5 4 3 2 11920 18 17 16 15 14 13 12 11MGreen/YellowDMT
0020140413_01 - 09/12 - Glow-worm11 Commissioning i IMPORTANT: At the time of commissioning, complete all relevant sections of the Benchmark Checkli
0020140413_01 - 09/12 - Glow-worm• Activate the Heating and Domestic Hot Water functions.• Run the appliance for at least 15 minutes, with a heating
0020140413_01 - 09/12 - Glow-worm11.6.2 Gas Rate• Make sure that all other gas burning appliances and pilot lights are o. • Check the gas rate usi
0020140413_01 - 09/12 - Glow-worm12.2 Installation settings• Push in and hold the button for more than 7 seconds to access the conguration menu.
0020140413_01 - 09/12 - Glow-wormCode Parameter Unit DescriptionFactory settingModiableparameterd.44 Digitalized ionisation voltage VDisplay the dig
0020140413_01 - 09/12 - Glow-worm12.5 Test modesBy activating these various test modes, you can enable special functions on the appliance.• Press th
0020140413_01 - 09/12 - Glow-wormMAINTENANCETo ensure the continued ecient and safe operation of the boiler it is recommended that it is checked and
INTRODUCTION1 Instructions guidance ...
0020140413_01 - 09/12 - Glow-worm14.2 Fault memory• This menu allows you to display the 10 most recent failure codes registered by the appliance.•
0020140413_01 - 09/12 - Glow-wormFault codesDescription Cause SolutionF61Fault in the main boardGas valve command fault• Check the main boards connect
0020140413_01 - 09/12 - Glow-worm14.4 Functionalowdiagram14.4.1 Central Heating14.4.2 Domestic Hot WaterMAINTENANCE- 30 -
0020140413_01 - 09/12 - Glow-worm15 Gas conversion adjustmentsIn order to operate with a gas other than that provided from the factory, it is necessa
0020140413_01 - 09/12 - Glow-worm15.1.2 Adjustingthemaximumpowersetting• Activate the test mode "P.01" and set the value to HI in ord
0020140413_01 - 09/12 - Glow-worm• To obtain service, please call your installer or Glow-worm’s own service organisation.PLEASE NOTE: During routine
0020140413_01 - 09/12 - Glow-worm17.2.2 Control box24V230V1Key1 Control box• Position the control box (1) into the service position.17.3 Combustio
0020140413_01 - 09/12 - Glow-wormG31 Burner % CO2Model Check (case on) Setting(caseo) CO/CO2 ratio2410.3 ± 0.3% 10.1 ± 0.2% 0.0042810.3 ± 0.3% 10.1
0020140413_01 - 09/12 - Glow-worm17.7 Condensate trapa Warning: condensate is mildly acidic. Use protective gloves.532416Key1 Condensate cleaning
0020140413_01 - 09/12 - Glow-worm17.8 Combustion block1011121314151617124356789Legend1 Gas valve connection2 Grounding cable3 Spark electrode inle
11 Commissioning ... 2111.1 S
0020140413_01 - 09/12 - Glow-worm17.8.2 Dismantling the burnerb Warning: The burner door seal (12) must be replaced each time the burner is dismantl
0020140413_01 - 09/12 - Glow-worm18.3 Viewingwindow24V230V34521Key1 Fibrewasher2 Steelwasher3 Glass4 Steelwasher5 Circlip• Remove the circ
0020140413_01 - 09/12 - Glow-worm18.4 Hydraulic block11169108762417131254211819212214152023325272630302829 Key1 Three-wayvalve2 Three-wayvalveel
0020140413_01 - 09/12 - Glow-worm18.4.2 Automatic air vent• Drain the boiler heating circuit as described in the appropriate chapter "Draining&
0020140413_01 - 09/12 - Glow-worm18.5 Combustion block2019181716151413121121102292325242627288302931327336543433637382351Legend1 Igniter unit retain
0020140413_01 - 09/12 - Glow-worm18.5.1 Spark electrode• Disconnect the electrode cap (7) and the earthing cable (6).• Remove the 2 spark electrode
0020140413_01 - 09/12 - Glow-worm18.5.9 Gas valve• Remove the burner door (11) refering to chapter "Dismantling the burner door".• Remove
0020140413_01 - 09/12 - Glow-worm18.7.2 2A Fuse Rating• For access, refer to chapter "Main PCB".• The fuse is located at top right hand s
0020140413_01 - 09/12 - Glow-worm• When ordering spare parts, contact Glow-worm’s own service organisation.• Please quote the name of the appliance
Manual HandlingIMPORTANT. With regards to the Manual Handling Operations, 1992 Regu-lations, the following lift operation exceeds the recommended weig
0020140413_01 - 09/12 - Glow-wormINTRODUCTION1 Instructions guidance1.1 Product documentationThe instructions are an integral part of the appliance
Declaration of ConformityInstallation,Commissioning andService Record
SERVICE INTERVAL RECORDIt is recommended that your heating system is serviced regularly and that you complete the appropriate Service Interval Record
SERVICE INTERVAL RECORDIt is recommended that your heating system is serviced regularly and that you complete the appropriate Service Interval Record
Subject to engineering changesGLOW-WORMNottingham Road, Belper, Derbyshire. DE56 1JTBecause of our constant endeavour for improvement, details may v
0020140413_01 - 09/12 - Glow-worm2.3 Regulation and statutory requirements2.3.1 CE MarkThis boiler meets the requirements of Statutory Instrument, N
0020140413_01 - 09/12 - Glow-worm3 Safety instructions and regulations3.1 Safety instructionsIf the gas pressure at the input of the appliance is ou
0020140413_01 - 09/12 - Glow-wormGas SupplyThe gas installation must be in accordance with the relevant standards.In GB, this is BS6891. In IE, this i
0020140413_01 - 09/12 - Glow-wormTECHNICAL DATA5 EasicomBoiler, type C13, C33, C43Description Unit 24 28Gas category ll2H3Pll2H3PSEDBUK rating 2009 %